TROUBLESHOOTING (Continued)
Up
TM-9-4910-663-34 Heater Immersion Liquid Fuel Fired 36 000 BTU Output for Corrugated Cans Manual
Next
TROUBLESHOOTING (Continued)

TM- 9-4910-663-34 Table 2-5.  TROUBLESHOOTING (Continued) MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Step 6.  Using ohmmeter, check for 1/4 ohm ±10% indication between REGULATOR B±  binding  post  anU REGULATOR CHECK FIXED RESISTANCE METHOD 1/4 OHM binding post. Replace resistor R10 if resistance is not as specified. 3.  DC VARIABLE POWER SUPPLY CIRCUITS a.    DC  VOLTAGE  AT  DC  VARIABLE  VOLTS  OUTPUT  BINDING  POSTS  CANNOT  BE  ADJUSTED  OVER  0  TO  32 VOLT RANGE. Step 1.  If DC voltage  at  DC  VARIABLE  VOLTS  OUTPUT  binding  posts  is  zero,  check  to  make  sure  that circuit breaker switch CB1, CIRCUIT BREAKERS CB2 DRIVE CONTROL circuit breaker, CIRCUIT BREAKERS  CB7  DC  VAR.    VOLTS  circuit  breaker,  CIRCUIT  BREAKERS  CB9  DC  VAR.    VOLTS circuit breaker, and DC VARIABLE VOLTS switch S10 are all set to ON position. Set switches and circuit breakers to ON position. Step  2.    Set  circuit  breaker  switch  CB1  to  OFF  position.    Using  ohmmeter,  check  for  continuity  across terminals of DC VARIABLE VOLTS switch S10 with switch set to ON position. Replace switch S10 if open indication is obtained. Step  3.    Using  ohmmeter,  check  for  continuity  across  terminals  of  CIRCUIT  BREAKERS  CB9  DC  VAR. VOLTS circuit breaker with circuit breaker set to ON position. Replace CIRCUIT BREAKER CB9 if open indication is obtained. Step 4.  Disconnect lead from one terminal of CIRCUIT BREAKERS CB7 DC VAR.  VOLTS circuit breaker. Using  ohmmeter,  check  for  continuity  across  terminals  of  CIRCUIT  BREAKER  CB7  with  circuit breaker set to ON position. Replace CIRCUIT BREAKER CB7 if open indication is obtained. Step  5.    Replace  lead  disconnected  in  step  4.    Disconnect  lead  from ±  terminal  of  rectifier  assembly  CR9 through 2-21

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing