TM5-4120-375-14
Table 4-2.
TROUBLESHOOTING (cont.)
MALFUCTION
TEST OR INSPECTION
CORRECTIVE ACTION
3.
INSUFFICIENT COOLING.
Step 1.
Check to see that thermostat (temperature control)
is set correctly.
Place thermostat in cooler position.
Replace defective thermostat in accordance
with paragraph 4-16.
Step 2.
Check for correct operation of evaporator fan
assembly.
Replace or repair damaged evaporator fan
assembly in accordance with paragraph 4-25.
4-15
|