Table 3-2. Troubleshooting

Figure 3­2. Servicing evaporator coil and condenser coil.
Section IV. TROUBLESHOOTING
3 - 1 1 . General
3­12. Troubleshooting Procedure
This section provides information useful in diag-
Malfunctions which may occur are listed in table
nosing and correcting unsatisfactory operation or
3­2. Each malfunction stated is followed by a list
failure of the air conditioner.
of probable causes of the trouble. The corrective
action recommended is described opposite the
probable cause.
Table 3-2. Troubleshooting
Malfunction
Probable cause
Corrective action
1. Compressor fails to start ----------------------- a. Selector switch improperly adjusted------------- a.
Set switch to COOL position.
b. Circuit breaker contacts open------------ b. Reset circuit breaker.
c. Contacts of high pressure cutout switch c. Push reset button to reset cutout switch.
open.
AGO 20053A